一、防爆壓力變送器規格參數有哪些
1、精度等級:0.25級基(ji)本誤差±0.25%、0.5級基(ji)本誤差±0.5%
2、非線性誤差:0.25級≤±0.25%FS、0.5級≤±0.5%FS
3、輸出特性:兩線制4-20mA輸(shu)出的(de)品種(zhong),標(biao)準供(gong)電(dian)(dian)DC24V,負載(zai)(zai)電(dian)(dian)阻(zu)大于600Ω時,每(mei)增(zeng)加50Ω需(xu)增(zeng)加1V供(gong)電(dian)(dian),但供(gong)電(dian)(dian)極限為DC45V,當需(xu)要(yao)超(chao)過DC24V供(gong)電(dian)(dian)時,輸(shu)出回路應避(bi)免長期工作在(zai)零負載(zai)(zai)電(dian)(dian)阻(zu)狀態,必要(yao)時可在(zai)輸(shu)出回路中串(chuan)入電(dian)(dian)阻(zu)以降低輸(shu)出功率管的(de)功耗,零負載(zai)(zai)電(dian)(dian)阻(zu)時供(gong)電(dian)(dian)電(dian)(dian)壓DC12V
4、模擬量:二(er)線制4~20mADC
5、數字量:兩線制4~20mADC并(bing)疊加符合HART協(xie)議的過程變(bian)量(liang)數(shu)字信號(hao)
6、電源:供(gong)電電壓(ya)12.5~45VDC
7、負載限制:回路(lu)***負(fu)載電(dian)(dian)阻(zu)Rmax取決(jue)于(yu)供電(dian)(dian)電(dian)(dian)壓(ya)。HART通(tong)訊要求負(fu)載電(dian)(dian)阻(zu)不低于(yu)250Ω,不高于(yu)600Ω。
7、通訊距離:RS485通訊距(ju)離為(wei)1.5Km,多站(zhan)通訊最多可接15臺智能變送器(qi)
8、輸出顯示:四(si)位(wei)制(zhi)數(shu)字顯(xian)(xian)示(shi)、五位(wei)LCD液晶顯(xian)(xian)示(shi)、指針式
9、防爆形式:本安型:ExiaII CT5,隔爆型
10、零點遷移范圍:零點可隨意正遷(qian)移或負(fu)遷(qian)移,但不得使設定(ding)的測(ce)量范(fan)圍上下限(xian)和量程超(chao)出極限(xian)值(zhi)。
11、溫度范圍:環境(jing)溫度:-40~85℃(選用LCD指示表時為-20~70℃)
12、測量介質溫度:-40~104℃
13、靜壓和單向超壓范圍:3.45Kpa(絕壓(ya))~31.2MPa(表壓(ya))
14、相對濕度:5~98%RH
15、啟動時間:5秒內啟動
16、容量變化量:小于0.16cm3
17、阻尼調整:時間(jian)常熟0.20~25秒
18、故障報警:如傳感(gan)器或電路出現(xian)故障(zhang),自(zi)動診斷功能將自(zi)動輸出3.9或21.0mA
19、組態保護:為(wei)了避免變(bian)送器的(de)組態數(shu)(shu)據(ju)被隨意改(gai)動,可(ke)通(tong)過軟件或保(bao)護(hu)開(kai)關鎖定存儲的(de)數(shu)(shu)據(ju)
二、防爆壓力變送器外殼是否需要接地
在《石油化工儀表工程施工技術規程》、《石油化工儀表接地設計規范》、《儀表系統接地設計規范》《自動化儀表工程施工及質量驗收規范》等規范中得出結論:防爆壓力變送器外殼是需要接地的。
1、供電(dian)(dian)電(dian)(dian)壓(ya)高于36V或有(you)可能帶有(you)危險電(dian)(dian)壓(ya)的(de)現場(chang)儀表(biao)金屬裸露部分正常不帶電(dian)(dian)的(de),均做保護接(jie)地。
2、供電電壓不高于(yu)36V的現場儀(yi)表金屬裸露部分,無特殊要求(qiu)時(shi),可不做保護接(jie)地。
3、非防爆危險區域的金(jin)屬(shu)盤(pan)、板上安裝的按(an)鈕、信號燈、繼電器(qi)等小(xiao)型低壓電器(qi)的金(jin)屬(shu)盤(pan)、板已良好接地,可(ke)不做(zuo)保(bao)護接地。
4、爆炸性(xing)危(wei)險環境的(de)電(dian)氣設備、電(dian)纜保(bao)護管、接線箱等金屬裸露部分(fen),均應接地。