一、避雷針的原理是什么
避(bi)雷(lei)針是根據尖端(duan)放(fang)電原(yuan)理制成的。避(bi)雷(lei)針是用(yong)來保護建筑(zhu)物、高大樹(shu)木等(deng)避(bi)免雷(lei)擊的裝(zhuang)置(zhi)。在(zai)被保護物頂端(duan)安裝(zhuang)一根接閃器,用(yong)符合(he)規(gui)格導線與埋(mai)在(zai)地(di)(di)下的泄流地(di)(di)網連接起來。
以避雷針作為接閃(shan)器的防(fang)雷電(dian)(dian)(dian)原理是:避(bi)雷針通(tong)過導(dao)線接入(ru)地(di)下(xia),與地(di)面形(xing)成等(deng)電(dian)(dian)(dian)位(wei)差,利用(yong)自(zi)身的高度(du),使電(dian)(dian)(dian)場強度(du)增加(jia)到極(ji)限(xian)值的雷電(dian)(dian)(dian)云電(dian)(dian)(dian)場發生畸變,開(kai)始電(dian)(dian)(dian)離(li)并下(xia)行先導(dao)放電(dian)(dian)(dian),避(bi)雷針在強電(dian)(dian)(dian)場作用(yong)下(xia)產生尖端(duan)放電(dian)(dian)(dian),形(xing)成向(xiang)(xiang)上先導(dao)放電(dian)(dian)(dian),兩(liang)者(zhe)會合形(xing)成雷電(dian)(dian)(dian)通(tong)路,隨之瀉入(ru)大地(di),達到避(bi)雷效果。實際上,避(bi)雷針是引雷針,可將周(zhou)圍的雷電(dian)(dian)(dian)引來并提前放電(dian)(dian)(dian),將雷電(dian)(dian)(dian)電(dian)(dian)(dian)流通(tong)過自(zi)身的接地(di)導(dao)體傳向(xiang)(xiang)地(di)面,避(bi)免(mian)保護對(dui)象直接遭雷擊。
二、避雷針的保護范圍是多少
避(bi)(bi)(bi)雷針的(de)工作原理就其本質而言,避(bi)(bi)(bi)雷針不是(shi)(shi)避(bi)(bi)(bi)雷,而是(shi)(shi)利用(yong)其高聳空中(zhong)的(de)有利地(di)位,把(ba)雷電引向自身,承受雷擊。同時(shi)把(ba)雷電流泄入大地(di),起著保護(hu)其附近比它矮的(de)建筑物或設備免受雷擊的(de)作用(yong)。簡單一點說,一級保護(hu)是(shi)(shi)以30米(mi)(mi)為半徑、二級保護(hu)是(shi)(shi)45米(mi)(mi)為半徑、三(san)級保護(hu)是(shi)(shi)60米(mi)(mi)為半徑做弧的(de)保護(hu)范圍。
1、計算方法
避雷針的(de)保護半徑與(yu)高(gao)度(h)有關,以及(ji)與(yu)所現的(de)滾(gun)球(qiu)半徑有關,D為滾(gun)球(qiu)半徑(閃擊距離)。
第一類建筑物為D=30米、第二(er)類建筑物為(wei)D=45米、第三類建筑物為(wei)D=60米。
2、保護范圍采用規范之計算公式:Rx=?{h(2hr-h)}-?{hx(2hr-hx)}。
(1)其中Rx為避(bi)雷針在距離地(di)面hx米(mi)處的保護(hu)半徑(米(mi))。
(2)hr為滾球半徑,根據(ju)建筑物類別取值30、45、60。
(3)hx為被保護物的高度。
一(yi)般(ban)來說(shuo),避雷針越高,保(bao)護范圍就越大(da),保(bao)護效果也越好,但考慮(lv)到(dao)避雷針建設的安(an)全性和(he)經(jing)濟(ji)性,避雷針大(da)多(duo)建設在(zai)35米(mi)-45米(mi)之間。